ISOLATING THREE PHASE TRANSFORMERS CLASS B FOR THE SUPPLY OF MEDICAL LOCATION

Transformers CBT series version for medical location is intended to be use for separation of circuits in hospital or medical environment. This type of transformers are built with double or reinforced insulation between circuits and between circuits and ground and provided with electrostatic shield between windings. Built with vector group YNyn0 and equipped with neutral terminal on primary and secondary winding to connect isolation control device by the end user. Version with or without PT100 temperature sensor to connect control device for winding temperature monitoring.

Technical data :

Standards : EN 61558-2-15 ; CEI 64-8/7; V2
Protection against electrical shock :  Class 1
Operating time : Continuos
Protection degree : IP 00
Terminals protecion degree : IP20
Max ambient temperature : +40° C
Thermal class : B – 130 ° C
Frequency : 50/60 Hz
Primary connection : YN
Secondary connection : yn
Electrostaic shield : Yes, between Primary and secondary windings